Abstract:
The paper presents some theoretical results regarding the subcooling
capabilities of a thermoelectric device. The refrigeration system taken into
account uses the R-134a refrigerant; a constant refrigerant flow of 1.4 m3/h
was considered for all the working variants. The CoolPack refrigeration
software was used in order to make the necessary calculations. A TEC 1
12710 type Peltier cooler was considered for subcooling of the liquid
refrigerant and its characteristics were evaluated based on experimental
tests. The subcooling temperature taken into account was comprised between
0 (no subcooling) and 10K; the cooling capacity, subcooling load and COP
were then calculated. The same refrigeration system equipped with a suction
gas heat exchanger (SGHX) was considered as reference. The Peltier cooler
achieved high COP (5.6…7.7) for low subcooling degrees (1…3K). The
overall COP of the refrigeration system with thermoelectric subcooling
reached a maximum COP of 2.507 for 5K subcooling and the cooling
capacity was comprised between 505 and 557 W. The use of SGHX led to
higher overall COP (2.56…2.79); in the meantime, a lower COP and cooling
capacity were obtained when no subcooling was applied (COP = 2.45; 0
Q
500 W).